ADAM-4018+ Functional Highlights For Industrial Temperature Monitoring
Eight Differential Thermocouple Input Channels For Multi Zone Systems
Provides 8 differential input channels for thermocouple measurement.
Channel independent configuration supports flexible multi sensor deployments.
Differential wiring improves noise immunity on long thermocouple runs.
Broad Thermocouple Type Coverage For Industrial Temperature Ranges
Supports thermocouple types J, K, T, E, R, S, B, and N.
Enables measurement from low temperature processes to high temperature furnaces depending on type.
Suitable for mixed thermocouple installations across different zones.
Thermocouple Burnout Detection For Better Fault Identification
Burnout detection is supported for all thermocouple inputs.
Helps identify broken sensors or open wiring conditions quickly.
Improves uptime through faster troubleshooting and maintenance response.
Modbus RTU And ASCII Command Support Over RS 485
Supports Modbus RTU for standardized industrial control integration.
Supports ASCII command mode for simpler serial control applications.
Designed for RS 485 multi drop networks used in distributed I O systems.
High Resolution Measurement With Industrial Grade Accuracy
Provides 16 bit resolution for detailed temperature acquisition.
Total sampling rate supports 10 samples per second across the module.
Typical accuracy is rated at ±0.1 percent or better in voltage mode and ±0.2 percent or better in current mode.
Isolation And Protection For Harsh Electrical Conditions
Isolation voltage is rated at 3,000 VDC.
Overvoltage protection supports up to ±35 VDC.
Built in TVS and ESD protection improves robustness against transient events.
ADAM-4018+ Technical Specifications Table For Modbus Thermocouple Inputs
| Specification | Details |
|---|---|
| Product Model | ADAM-4018+ |
| Module Type | 8 channel Thermocouple Input Module with Modbus |
| Network Interface | RS 485 |
| Supported Protocols | ASCII command and Modbus RTU |
| Input Channels | 8 differential channels |
| Channel Independent | Yes |
| Input Types | Thermocouple, mV, V, mA |
| Input Ranges | 0 to 100 mV, 0 to 500 mV, 0 to 1 V, 0 to 2.5 V, 0 to 5 V, 0 to 10 V, plus or minus 100 mV, plus or minus 500 mV, plus or minus 1 V, plus or minus 2.5 V, plus or minus 5 V, plus or minus 10 V, plus or minus 20 mA, 0 to 20 mA, 4 to 20 mA |
| Thermocouple Types | J, K, T, E, R, S, B, N |
| Temperature Ranges | J 0 to 760°C, K 0 to 1370°C, T -100 to 400°C, E 0 to 1000°C, R 500 to 1750°C, S 500 to 1750°C, B 500 to 1800°C, N -200 to 1300°C |
| Burnout Detection | 4 to 20 mA and all thermocouple types |
| Input Impedance | Voltage 20 MΩ, Current 120 Ω |
| Resolution | 16 bit |
| Sampling Rate | 10 samples per second total |
| Isolation Voltage | 3,000 VDC |
| Overvoltage Protection | ±35 VDC |
| CMR At 50/60 Hz | 120 dB |
| NMR At 50/60 Hz | 100 dB |
| Span Drift | ±25 ppm per °C typical |
| Zero Drift | ±6 µV per °C |
| Watchdog Timer | System and communication, 1.6 second |
| Power Input | Unregulated 10 to 30 VDC |
| Power Consumption | 1.0 W at 24 VDC |
| Connectors | 2 plug in terminal blocks, #14 to 22 AWG |
| Operating Temperature | -10 to 70°C |
| Operating Humidity | 5 to 95 percent RH |
| Storage Temperature | -25 to 85°C |
| Ordering Information | ADAM-4018+-F |
Suitable Applications For ADAM-4018+ Thermocouple Input Modules With Modbus
The ADAM-4018+ is well suited for distributed multi point temperature monitoring where thermocouple sensors must be acquired over RS 485 networks with Modbus RTU. Its broad thermocouple support, channel independent configuration, and built in protection make it a strong choice for remote industrial temperature measurement.
Multi zone furnace, kiln, and oven temperature monitoring
Heat treatment and thermal processing lines using thermocouples
Process skids requiring Modbus RTU temperature acquisition over RS 485
Energy systems and boilers monitoring high temperature points
Plastics and extrusion equipment monitoring barrel and die temperatures
Remote panels where thermocouple wiring runs are long and noise susceptible
Industrial SCADA temperature trending using Modbus RTU networks
OEM packaged equipment requiring compact thermocouple input modules