ADAM-4060 Relay Output Module Advantages
Four Flexible Relay Output Channels
The ADAM-4060 incorporates two Form A and two Form C relay channels to provide versatile switching options for industrial control circuits.AC And DC Load Switching Capability
The relay contacts support compatible resistive loads up to 0.6 A at 125 VAC, 0.3 A at 250 VAC, 2 A at 30 VDC, and 0.6 A at 110 VDC.Modbus RTU And ASCII Protocol Support
The module communicates using Modbus RTU and ASCII command protocols, allowing straightforward integration with RS-485 automation networks.500 VAC Relay Breakdown Voltage
A 500 VAC breakdown voltage helps support electrical separation and dependable relay operation in industrial applications.Fast Relay Response Times
Typical relay on time is 4 ms and typical relay off time is 5 ms, supporting responsive control of connected devices.Built In System Watchdog Timer
A 1.6 second system watchdog timer helps monitor module operation for improved control system reliability.Low Power Industrial I/O Design
The ADAM-4060 consumes 0.9 W at 24 VDC typically and 1.3 W at 24 VDC maximum, helping reduce power demand in remote I/O installations.
ADAM-4060 Relay Output Technical Specifications
| Specification | Details |
|---|---|
| Product Model | ADAM-4060 |
| Module Type | Relay output module |
| Relay Output Channels | 4 |
| Relay Contact Configuration | 2 Form A and 2 Form C |
| Supported Protocols | ASCII command and Modbus RTU |
| Relay Breakdown Voltage | 500 VAC, 50 or 60 Hz |
| Contact Rating At 125 VAC | 0.6 A resistive |
| Contact Rating At 250 VAC | 0.3 A resistive |
| Contact Rating At 30 VDC | 2 A |
| Contact Rating At 110 VDC | 0.6 A |
| Initial Insulation Resistance | 100 MΩ minimum at 500 VDC |
| Typical Relay On Time | 4 ms |
| Typical Relay Off Time | 5 ms |
| Maximum Operating Speed | 20 operations per minute at rated load |
| Power Input | Unregulated 10 to 30 VDC |
| Power Consumption | 0.9 W at 24 VDC typical, 1.3 W at 24 VDC maximum |
| Watchdog Timer | System, 1.6 seconds |
| Connectors | 2 plug in terminal blocks |
| Wire Size | #14 to #22 AWG |
| Operating Temperature | -10 to 70°C |
| Storage Temperature | -25 to 85°C |
| Operating Humidity | 5 to 95% RH |
| Certifications | FCC, CE |
Ideal Uses For The ADAM-4060 Remote Relay Module
The ADAM-4060 is well suited for applications requiring remotely controlled relay outputs on an RS-485 network. Its combination of Form A and Form C contacts, Modbus RTU support, and AC and DC switching capability makes it effective for industrial machinery, building systems, and distributed equipment control.
Suitable applications include:
Remote relay and contactor control
Solenoid valve switching
Alarm and annunciator activation
Industrial indicator light control
Pump and fan control interfaces
Building automation control panels
Machine control and equipment sequencing
PLC and SCADA relay output expansion
Process automation switching circuits
Test equipment and remote control panels