ADAM-6052 Ethernet Digital I/O Module Features
Eight Digital Inputs For Flexible Field Signal Monitoring
The ADAM-6052 provides eight digital input channels for monitoring switches, contacts, sensors, alarms, and status signals. Inputs support dry and wet contact operation, with selection determined by switch or jumper configuration.Eight Source Type Outputs For Direct Device Control
Eight source type digital output channels provide 10 to 35 VDC operation with up to 1 A per channel. This output capability supports control of compatible loads such as indicators, relays, solenoids, and other DC actuators.High Speed Counter Frequency And Pulse Functions
Digital inputs support 3 kHz counter input and 3 kHz frequency input functions with a 32 bit counter plus one bit overflow. Digital outputs support pulse output up to 5 kHz, along with configurable high to low and low to high delay output functions.Peer To Peer And Graphic Condition Logic Control
Built in Peer to Peer functionality enables direct channel mapping between compatible I/O modules. Graphic Condition Logic provides a graphical method for configuring control rules without additional controllers or programming. Only one of these functions can be enabled at a time.Isolated Ethernet Connectivity For Industrial Networks
A 10/100Base T(X) Ethernet port supports Modbus TCP, TCP/IP, UDP, and RESTful communication. D version models also support MQTT and SNMP protocols for expanded monitoring and IoT connectivity.Industrial Protection For Reliable Deployment
The ADAM-6052 includes 2,000 VDC isolation protection and power reversal protection. Output overcurrent protection further supports reliable operation when controlling connected field devices.
ADAM-6052 Source Type Digital I/O Technical Specifications
| Specification | ADAM-6052 Details |
|---|---|
| Product Type | 16 channel source type isolated digital I/O Modbus TCP module |
| Ethernet Interface | 1 port 10/100Base T(X) |
| Digital Input Channels | 8 |
| Digital Output Channels | 8 source type |
| Digital Input Type | Dry or wet contact, selected by switch or jumper |
| Dry Contact Logic | Logic 0 open, Logic 1 closed to GND |
| Wet Contact Logic | Logic 0: 0 to 3 VDC or floating. Logic 1: 10 to 30 VDC |
| Supported Input Types | Sink NPN and source PNP compatible |
| Counter Input | 3 kHz, 32 bit plus 1 bit overflow |
| Frequency Input | 3 kHz |
| Counter Value Retention | Keep or discard counter value when power is removed |
| Digital Output Voltage Range | 10 to 35 VDC |
| Output Current | 1 A per channel |
| Output Functions | Pulse output up to 5 kHz, high to low delay, low to high delay |
| Output Protection | Overcurrent protection |
| Isolation Protection | 2,000 VDC |
| Power Input | 10 to 30 VDC |
| Power Consumption | 2 W at 24 VDC |
| Communication Protocols | Modbus TCP, TCP/IP, UDP, RESTful. MQTT and SNMP on D version models |
| Control Functions | Peer to Peer and Graphic Condition Logic |
| Watchdog | System watchdog at 1.6 seconds and programmable communication watchdog |
| Connector Type | RJ 45 Ethernet port and plug in screw terminal block for I/O and power |
| Operating Temperature | Minus 20 to 70°C. D version: minus 40 to 70°C |
| Storage Temperature | Minus 30 to 80°C. D version: minus 40 to 85°C |
| Operating Humidity | 20 to 95% RH, non condensing |
| Storage Humidity | 0 to 95% RH, non condensing |
| Certifications | FCC, CE, UL, Class I Division 2 Groups A, B, C, and D hazardous locations |
| Dimensions | 70 x 120 x 30 mm |
| Enclosure | ABS and PC |
| Mounting Options | DIN 35 rail, stack, or wall mounting |
ADAM-6052 Source Type Ethernet I/O Applications
The ADAM-6052 is suitable for distributed industrial control systems that require reliable monitoring of digital status signals and source type DC output control. Its Ethernet connectivity, isolated I/O, counter capabilities, and standalone logic functions make it well suited for installations that need to reduce controller dependency while maintaining network level visibility.
Suitable applications include:
Remote machine status monitoring and actuator control
Factory automation and production line control
Industrial alarm and annunciation systems
Material handling and conveyor control
Packaging equipment monitoring
Pump, valve, and solenoid control
Building automation systems
Energy management and equipment status monitoring
Remote I/O expansion for Modbus TCP networks
SCADA and network management system integration
Hazardous location installations requiring Class I Division 2 suitability