The Short Answer
Both systems classify locations where explosive gas, vapor or dust may be present. The Class/Division system, set out in NEC Article 500, is traditional in North America and uses two divisions. The Zone system, used by IEC, ATEX and NEC Article 505/506, uses three zones based on how often the hazard is present. Equipment must be approved for the system and level used at your site.
The Class/Division System
- Class I: flammable gases and vapors.
- Class II: combustible dusts.
- Class III: ignitable fibers and flyings.
- Division 1: the hazard is present in normal operation.
- Division 2: the hazard is present only under abnormal conditions, such as a leak.
The Zone System
- Zone 0 (gas) / Zone 20 (dust): hazard present continuously or for long periods.
- Zone 1 / Zone 21: hazard likely in normal operation.
- Zone 2 / Zone 22: hazard not likely, and only for short periods if it occurs.
How They Compare
Zone 0
Within
Division 1
Zone 1
Within
Division 1
Zone 2
Equivalent to
Division 2
Division 1 covers both Zone 0 and Zone 1. Equipment approved for Division 1 is generally acceptable in Zone 1, but Zone 0 needs equipment specifically approved for continuous hazards, such as intrinsically safe “ia” equipment.
What It Means When Buying Equipment
- Confirm whether your site uses Class/Division or Zone classification.
- Check the Class, Division or Zone, gas group and temperature class (T-code) on the label.
- Look for the protection method, such as intrinsic safety, explosion-proof or non-incendive.
- Match certifications to the region, for example UL/CSA in North America and ATEX/IECEx elsewhere.
Related Products
We supply sensors and networking equipment approved for hazardous locations.
Frequently Asked Questions
Is Class I Division 2 the same as Zone 2?
They are broadly equivalent for gases, but the certification marking differs, so check the equipment is approved under the system your site uses.
What is a temperature class (T-code)?
It is the maximum surface temperature of the equipment. T4, for example, means 135 °C or below, and it must be below the ignition temperature of the gas present.
Can I use ATEX-approved equipment in the US?
Not automatically. US installations normally require equipment listed under NEC-recognized standards, though many products carry both approvals.