The Short Answer
A single-ended input measures a signal against a common ground shared by all channels. It gives you more channels per card, but it is more sensitive to noise and ground differences. A differential input measures the voltage between two dedicated wires, so noise and ground offsets that affect both wires cancel out. Use differential inputs for low-level signals, long cables and noisy environments.
How Each Input Works
Single-ended
- Each signal uses one input plus a shared ground.
- Twice as many channels on the same card.
- Any ground difference adds to the reading.
- Fine for strong signals over short cables.
Differential
- Each signal uses two inputs: positive and negative.
- Half the channel count.
- Rejects common-mode noise and ground offsets.
- Best for low-level signals and long cables.
Common-Mode Rejection
Noise picked up along a cable usually appears equally on both wires. A differential input subtracts one wire from the other, so this common-mode voltage cancels. The common-mode rejection ratio (CMRR), often 80 dB or more, tells you how well an input does this. Every input also has a common-mode voltage range, and signals outside it will read incorrectly, which is where isolation helps.
When to Use Each
- Single-ended: 0-10 V signals from sensors in the same cabinet, sharing the same power supply.
- Differential: thermocouples, strain gauges and other millivolt signals.
- Differential: sensors powered from a separate supply or located in another building.
- Isolated differential: high common-mode voltages or severe electrical noise.
Pseudo-Differential Inputs
Some cards offer a pseudo-differential mode, where every channel shares a common reference that is separate from the card ground. It offers better noise rejection than single-ended while keeping a higher channel count, and suits groups of sensors that share one reference.
Related Products
We supply DAQ cards and remote I/O with single-ended, differential and isolated analog inputs.
Frequently Asked Questions
Can I use differential inputs for a 4-20 mA signal?
Yes. Place a precision shunt resistor across the two inputs, or use a card with built-in current inputs.
Why do my single-ended readings change when I connect another sensor?
Shared ground currents create voltage drops that appear in the readings. Differential or isolated inputs fix this.
How many channels do I lose with differential inputs?
Usually half. A 16-channel single-ended card typically provides 8 differential channels.