The Short Answer
A process meter (or panel meter) reads an analog signal, such as 4-20 mA or 0-10 V, and displays it in real engineering units, such as psi, ft, gpm or °F. Scaling tells the meter what to show at the bottom and top of the input range. For example, you set 4 mA to display 0.0 and 20 mA to display 150.0 for a 0-150 psi transmitter.
What a Process Meter Does
- Displays a process signal in real units on a panel, wall or field enclosure.
- Drives relay alarms at high and low set points.
- Retransmits the signal as an isolated 4-20 mA or 0-10 V output.
- Shares readings over Modbus RS-485.
- Supplies 24 VDC excitation to power a 2-wire transmitter.
Scaling Step by Step
- Set the input type, for example 4-20 mA.
- Set the decimal point position, for example 000.0.
- Set the low display value, shown at 4 mA, for example 0.0.
- Set the high display value, shown at 20 mA, for example 150.0.
- Check the reading against a known input or calibrator.
Display = Low value + (Input − 4 mA) ÷ 16 mA × (High value − Low value)
Worked Example: Tank Level
A level transmitter outputs 4-20 mA for 0 to 12 ft of water. To display the level in feet, set 4 mA to 0.0 and 20 mA to 12.0. At 12 mA, halfway through the signal range, the meter shows 6.0 ft. To display gallons instead, multiply both values by the tank’s gallons per foot, as long as the tank has vertical sides. Many meters also support multi-point linearization for horizontal cylinders and other shapes.
Loop-Powered vs Externally Powered Meters
Loop-powered
- Powered by the 4-20 mA loop itself.
- No extra wiring or supply needed.
- Adds a voltage drop to the loop budget.
- Ideal for field-mounted displays.
Externally powered
- Needs an AC or DC supply.
- Can include relays, retransmission and Modbus.
- Often provides transmitter excitation.
- Ideal for control panels.
Related Products
We supply loop-powered displays, large-digit wall meters and programmable process meters.
Frequently Asked Questions
Can a process meter display negative values?
Yes. Set the low display value to a negative number, for example -50.0 for a temperature range of -50 to 150 °F.
How much voltage does a loop-powered display use?
Typically 1 to 3 V, which must be included in the loop power budget.
Can I scale a meter without a calibrator?
Yes. Most meters let you enter the scaling values directly from the keypad. A calibrator is only needed to verify the result.