Signal Conditioning & Isolation

How signal converters, isolators and splitters convert, scale and protect process signals, and why galvanic isolation solves so many wiring problems.

Articles in This Category

How Do I Convert 4-20 mA to 0-10 V?

The reliable way to convert 4-20 mA to 0-10 V is with a signal converter, which scales 4 mA to 0 V and 20 mA to 10 V and isolates the two circuits. A 500 Ω resistor across the input gives 2-10 V, not 0-10 V, so the receiver must be scaled to match, and there is no isolation. A 250 Ω resistor gives 1-5 V for inputs that accept it.

What Is Galvanic Isolation, and Why Does It Matter?

Galvanic isolation separates two electrical circuits so that no current can flow directly between them, while the signal still passes across. Isolators do this with a transformer, an optocoupler or a capacitive barrier. In instrumentation, isolation removes ground loops, blocks common-mode noise, and protects control equipment from surges and faults in the field.