The Short Answer
The reliable way to convert 4-20 mA to 0-10 V is with a signal converter, which scales 4 mA to 0 V and 20 mA to 10 V and isolates the two circuits. A 500 Ω resistor across the input gives 2-10 V, not 0-10 V, so the receiver must be scaled to match, and there is no isolation. A 250 Ω resistor gives 1-5 V for inputs that accept it.
Option 1: A Resistor
Ohm’s law turns current into voltage. Placing a precision resistor across a voltage input converts the loop current into a voltage:
Voltage = Current × Resistance
250 Ω
4-20 mA becomes
1-5 V
500 Ω
4-20 mA becomes
2-10 V
This is inexpensive but limited. The output never reaches 0 V, the resistor adds to the loop burden, the receiver must be rescaled, and there is no isolation, so ground loops remain a risk.
Option 2: Reconfigure the Input
Many PLC and controller inputs can be switched between current and voltage modes. If your input supports 4-20 mA directly, use it. Changing the receiver is often simpler than converting the signal.
Option 3: An Isolated Signal Converter
A signal converter receives the 4-20 mA signal and outputs a true 0-10 V signal, with full scaling from 0 V at 4 mA to 10 V at 20 mA. It also galvanically isolates the input, output and power supply, which removes ground loop problems and protects both devices.
- True 0-10 V output, so no rescaling needed.
- Isolation eliminates ground loops.
- Drives the voltage input properly, even with several receivers.
- DIN-rail mounting alongside other panel components.
Choosing a Converter
- Input and output ranges, including any special ranges such as 0-5 V or 1-5 V.
- Whether the 4-20 mA input is loop-powered or sourced.
- Supply voltage available in the panel.
- Isolation level, accuracy and response time.
Related Products
Our signal converters cover 4-20 mA, 0-20 mA, 0-10 V, 0-5 V and 1-5 V, with sink and source outputs.
Frequently Asked Questions
Can I convert 0-10 V to 4-20 mA?
Yes. Signal converters work in both directions. A 0-10 V input to 4-20 mA output converter lets voltage sensors drive long cable runs.
Why does my resistor conversion read 2 V at zero?
A 500 Ω resistor turns 4 mA into 2 V. Scale the receiver for 2-10 V, or use a signal converter for true 0-10 V.
Does a converter need its own power supply?
Most do, typically 24 VDC. Some loop-powered isolators take power from the 4-20 mA loop instead.