The Short Answer
Galvanic isolation separates two electrical circuits so that no current can flow directly between them, while the signal still passes across. Isolators do this with a transformer, an optocoupler or a capacitive barrier. In instrumentation, isolation removes ground loops, blocks common-mode noise, and protects control equipment from surges and faults in the field.
How Isolation Works
- Transformer coupling: the signal is modulated, passed through a transformer and demodulated. Common in high-accuracy analog isolators.
- Optical coupling: an LED and photodetector carry the signal as light. Common in digital I/O.
- Capacitive coupling: a high-frequency signal crosses a thin insulating barrier inside an integrated circuit.
Whatever the method, the input and output sides have no conductive path between them, and are rated to withstand a test voltage, often 1,500 V or more.
Problems Isolation Solves
- Ground loops between field instruments and control panels on different grounds.
- Common-mode voltage that would otherwise exceed an input card’s limits.
- Electrical noise from drives, welders and power cables.
- Damage from surges, lightning or wiring faults spreading into the control system.
- Connecting one signal to two systems that cannot share a ground.
Types of Isolation in a Signal Converter
2-way isolation
- Input is isolated from output.
- Power supply shares a reference with one side.
- Suits most simple loops.
3-way (full) isolation
- Input, output and power supply are all isolated from each other.
- Best protection against ground loops.
- Recommended where devices sit on different grounds.
Reading an Isolation Rating
Datasheets usually give a test voltage, such as 1.5 kV or 3 kV AC for one minute, and a working voltage, the voltage the barrier can handle continuously. Choose an isolator whose working voltage exceeds any ground potential differences you expect in service.
Related Products
Our galvanically isolated signal converters fit on a DIN rail and handle the most common process signals.
Frequently Asked Questions
Does isolation reduce accuracy?
A quality isolator adds very little error, typically ±0.1% of span or better.
Is a loop-powered isolator isolated?
Yes. A loop-powered isolator takes its power from the input loop and still isolates the input from the output.
Do I need isolation for every analog signal?
No, but it is strongly recommended where devices sit on different grounds, cables run between buildings, or the environment is electrically noisy.