The Short Answer
Choose 4-20 mA for long cable runs, electrically noisy plants and anywhere you need to detect a broken wire. Choose 0-10 V for short runs inside a panel or machine, where its simpler wiring and direct compatibility with many controllers and drives are an advantage.
How Each Signal Works
A 4-20 mA output is a current signal. The transmitter regulates the current in a series loop, and the receiver measures it. Because current is the same at every point in a series circuit, the reading does not change with cable length or connection resistance.
A 0-10 V output is a voltage signal. The sensor sets a voltage between its output and common, and the receiver measures that voltage with a high-impedance input. Any voltage dropped along the cable, or picked up as noise, appears directly as measurement error.
Side-by-Side Comparison
4-20 mA
- Accurate over thousands of feet of cable.
- Strong immunity to electrical noise.
- Live zero: 0 mA reveals a broken wire.
- 2-wire loop-powered designs save cabling.
- Needs a loop power budget calculation.
0-10 V
- Best for runs under about 50 ft (15 m).
- More susceptible to noise and ground offsets.
- 0 V looks the same as a broken wire.
- Usually 3-wire: supply, signal and common.
- Easy to read and to connect several receivers in parallel.
When to Use 4-20 mA
- Process plants, water and wastewater, oil and gas, and other sites with long cable runs.
- Areas with variable frequency drives, welders or large motors that generate electrical noise.
- Safety and quality-critical measurements, where a wiring fault must be detected.
- Hazardous areas that use intrinsically safe loops.
When to Use 0-10 V
- Short connections inside a control panel, machine or skid.
- HVAC and building automation, where 0-10 V is the common standard.
- Driving the analog speed reference on many motor drives.
- OEM equipment, where the sensor and controller sit close together.
Related voltage ranges include 0-5 V, 1-5 V and ratiometric 0.5-4.5 V, which is common on OEM and mobile hydraulic pressure sensors.
Converting Between the Two
If a sensor and a controller use different signals, a signal converter translates one to the other and isolates the two circuits at the same time. A simple 500 Ω resistor will turn 4-20 mA into 2-10 V, but it loses the bottom of the range and offers no isolation, so it is only suitable for non-critical work.
Related Products
Most of our sensors are available with either output. Choose the one that matches your receiver and installation.
Frequently Asked Questions
Is 4-20 mA more accurate than 0-10 V?
At the sensor, both can be equally accurate. In the field, 4-20 mA usually delivers better accuracy because cable resistance and noise do not affect a current signal.
How far can a 0-10 V signal travel?
For good accuracy, keep 0-10 V runs short, typically under 50 ft (15 m), using shielded cable. Beyond that, use 4-20 mA.
Can I connect a 0-10 V sensor to a 4-20 mA input?
Not directly. Use a signal converter, or change the input card to voltage mode if it supports both.