4-20 mA vs 0-10 V: Which Analog Output Should You Choose?

The Short Answer

Choose 4-20 mA for long cable runs, electrically noisy plants and anywhere you need to detect a broken wire. Choose 0-10 V for short runs inside a panel or machine, where its simpler wiring and direct compatibility with many controllers and drives are an advantage.

How Each Signal Works

A 4-20 mA output is a current signal. The transmitter regulates the current in a series loop, and the receiver measures it. Because current is the same at every point in a series circuit, the reading does not change with cable length or connection resistance.

A 0-10 V output is a voltage signal. The sensor sets a voltage between its output and common, and the receiver measures that voltage with a high-impedance input. Any voltage dropped along the cable, or picked up as noise, appears directly as measurement error.

Side-by-Side Comparison

4-20 mA

0-10 V

When to Use 4-20 mA

When to Use 0-10 V

Related voltage ranges include 0-5 V, 1-5 V and ratiometric 0.5-4.5 V, which is common on OEM and mobile hydraulic pressure sensors.

Converting Between the Two

If a sensor and a controller use different signals, a signal converter translates one to the other and isolates the two circuits at the same time. A simple 500 Ω resistor will turn 4-20 mA into 2-10 V, but it loses the bottom of the range and offers no isolation, so it is only suitable for non-critical work.

Related Products

Most of our sensors are available with either output. Choose the one that matches your receiver and installation.

Available with 4-20 mA, 0-10 V and other outputs. View range

Current and voltage output level transmitters. View range

Convert 4-20 mA to 0-10 V and back, with isolation. View range

Frequently Asked Questions

At the sensor, both can be equally accurate. In the field, 4-20 mA usually delivers better accuracy because cable resistance and noise do not affect a current signal.

For good accuracy, keep 0-10 V runs short, typically under 50 ft (15 m), using shielded cable. Beyond that, use 4-20 mA.

Not directly. Use a signal converter, or change the input card to voltage mode if it supports both.

More in This Category

What Is a 4-20 mA Signal?

A 4-20 mA signal is an analog DC current that represents a measured value, with 4 mA at the bottom of the range and 20 mA at the top. Because it is a current rather than a voltage, it travels long distances without losing accuracy, and the same two wires can power the sensor.

2-Wire vs 3-Wire vs 4-Wire Transmitters: What Is the Difference?

All three transmit the same 4-20 mA signal. The difference is how they get power. A 2-wire transmitter draws its power from the signal loop itself. A 3-wire transmitter has a separate supply wire and shares a common return with the signal. A 4-wire transmitter has completely separate power and signal pairs, so it can use much more power, including AC mains.

What Is HART, and How Does It Work Over a 4-20 mA Loop?

HART (Highway Addressable Remote Transducer) is a digital protocol that rides on top of a standard 4-20 mA signal. It superimposes a small, high-frequency signal on the loop current, so the analog value keeps working while a HART device can also exchange configuration settings, diagnostics and extra measurements over the same two wires.

Need help choosing the right product?

Our engineers can help you select, configure and integrate the right sensor, instrument or industrial computer for your application.