The Short Answer
Modbus RTU and Modbus TCP use the same registers and function codes. The difference is how messages travel. Modbus RTU sends compact binary messages over a serial link, usually RS-485. Modbus TCP wraps the same messages in TCP/IP packets and sends them over standard Ethernet.
What Is Modbus?
Modbus is an open, master-slave (client-server) protocol created in 1979 for industrial controllers. A master requests data, and each slave device answers from a table of numbered registers: coils and discrete inputs for on/off values, and input and holding registers for 16-bit numbers. Its simplicity is why so many sensors, meters, drives and controllers support it.
Modbus RTU
Modbus RTU runs over serial links, most often RS-485. Every message carries a slave address (1 to 247) and a CRC checksum, and devices are wired in a daisy chain on a single twisted pair.
- Up to 32 standard unit loads per RS-485 segment, and up to 4,000 ft (1,200 m) of cable.
- Typical speeds of 9,600 to 115,200 bit/s.
- Low cost and very low power, ideal for sensors and remote sites.
- One master per network, and only one message on the line at a time.
Modbus TCP
Modbus TCP carries the same request and response data inside TCP/IP, normally on port 502. The checksum is dropped because Ethernet handles error checking, and devices are addressed by IP address.
- Runs on standard Ethernet switches, fiber and wireless networks.
- Much higher throughput, with several clients able to poll at once.
- Easy to integrate with SCADA, HMIs and IT systems.
- Needs network design and cybersecurity like any other Ethernet device.
Connecting RTU Devices to a TCP Network
A Modbus gateway, often built into a serial device server, translates between the two. The SCADA system talks Modbus TCP to the gateway, and the gateway polls the RS-485 devices using Modbus RTU. This lets you keep low-cost serial sensors in the field while integrating them with modern Ethernet systems.
Which Should You Choose?
Choose Modbus RTU for sensors, meters and remote I/O spread over a long cable run, especially where power and cost must be low. Choose Modbus TCP for controllers, HMIs and devices already on an Ethernet network, or where many clients need the data.
Related Products
We supply Modbus sensors, remote I/O modules and the gateways that connect them.
Frequently Asked Questions
Can Modbus RTU and Modbus TCP devices talk directly?
No. They use different transports, so you need a Modbus gateway between them.
What is Modbus ASCII?
An older serial variant that sends messages as readable text. It is slower than RTU and is rarely used in new systems.
How many devices can be on a Modbus RTU network?
Addresses run from 1 to 247, but a standard RS-485 segment supports 32 unit loads. Repeaters or fractional-load transceivers extend this.