What Is RS-485, and How Do I Wire and Terminate It?

The Short Answer

RS-485 is a differential serial standard that sends data as the voltage difference between two wires, usually labeled A and B. That makes it highly resistant to noise and lets one twisted pair link up to 32 standard devices over about 4,000 ft (1,200 m). For reliable communication, wire the devices in a daisy chain and fit a 120 Ω terminating resistor at each end of the cable.

How RS-485 Works

Instead of measuring a signal against ground, an RS-485 receiver looks at the difference between line A and line B. Noise picked up along the cable affects both wires almost equally, so it cancels out. A difference of at least 200 mV is read as a valid logic state.

RS-485 is a physical layer only. Protocols such as Modbus RTU, PROFIBUS DP and BACnet MS/TP define what the messages mean.

Wiring Rules

Termination and Biasing

A termination resistor of 120 Ω across A and B at both physical ends of the cable matches the cable impedance and stops signals reflecting back down the line. Do not fit terminators at devices in the middle of the bus.

Bias (fail-safe) resistors hold the line in a known idle state when no device is transmitting. They are usually fitted once, at the master, and many converters and PLC ports include them as a switchable option.

120 Ω

Termination at
each end

32

Standard unit
loads per segment

4,000 ft

Max cable length
at low baud rates

Speed vs Distance

Longer cables mean lower maximum data rates. A rough guide is that the product of cable length in meters and data rate in bit/s should stay below about 108. At 9,600 bit/s, the full 1,200 m is achievable. At 1 Mbit/s, keep the cable to about 100 m.

Troubleshooting RS-485 Problems

Related Products

We supply RS-485 converters, isolators and serial servers, plus sensors and remote I/O with RS-485 outputs.

Connect RS-485 devices to Ethernet networks. View range

RS-485 Modbus remote I/O modules. View range

Level transmitters with RS-485 digital output. View range

Frequently Asked Questions

On very short runs at low baud rates it may work without, but fitting termination at both ends is good practice and prevents intermittent faults.

2-wire (half-duplex) uses one pair for both directions. 4-wire (full-duplex) uses separate transmit and receive pairs. Most Modbus networks use 2-wire.

The standard defines A as the inverting line, but many manufacturers label it the other way round. If a device will not communicate, try swapping A and B.

More in This Category

What Is a 4-20 mA Signal?

A 4-20 mA signal is an analog DC current that represents a measured value, with 4 mA at the bottom of the range and 20 mA at the top. Because it is a current rather than a voltage, it travels long distances without losing accuracy, and the same two wires can power the sensor.

2-Wire vs 3-Wire vs 4-Wire Transmitters: What Is the Difference?

All three transmit the same 4-20 mA signal. The difference is how they get power. A 2-wire transmitter draws its power from the signal loop itself. A 3-wire transmitter has a separate supply wire and shares a common return with the signal. A 4-wire transmitter has completely separate power and signal pairs, so it can use much more power, including AC mains.

4-20 mA vs 0-10 V: Which Analog Output Should You Choose?

Choose 4-20 mA for long cable runs, electrically noisy plants and anywhere you need to detect a broken wire. Choose 0-10 V for short runs inside a panel or machine, where its simpler wiring and direct compatibility with many controllers and drives are an advantage.

Need help choosing the right product?

Our engineers can help you select, configure and integrate the right sensor, instrument or industrial computer for your application.