What Is a 4-20 mA Signal?

The Short Answer

A 4-20 mA signal is an analog DC current that represents a measured value. The transmitter sends 4 mA at the bottom of its range and 20 mA at the top, with every value in between scaled in a straight line. Because the signal is a current rather than a voltage, it travels hundreds or thousands of feet without losing accuracy, it shrugs off electrical noise, and the same two wires can power the sensor. That combination has made 4-20 mA the most widely used signal in process instrumentation.

How a 4-20 mA Current Loop Works

A 4-20 mA signal travels around a current loop: a single series circuit in which the same current flows through every component. Because nothing branches off, the current measured at the control room is exactly the current set by the transmitter in the field, no matter how long the cable is.

A typical loop has four parts:

The transmitter does not generate the current itself. It acts like a precise, variable valve: the power supply provides the energy, and the transmitter limits the current to the value that matches the reading. That is why most 4-20 mA transmitters are described as loop-powered or 2-wire devices.

Why Does the Signal Start at 4 mA Instead of 0 mA?

Starting the range at 4 mA, known as a live zero, solves two practical problems:

  • Fault detection. If a wire breaks or the transmitter loses power, the current drops to 0 mA. Because a genuine zero reading is 4 mA, the receiver can tell the difference between “the tank is empty” and “the loop is broken”.
  • Powering the transmitter. A loop-powered transmitter takes its operating power from the loop current. Keeping at least 4 mA flowing at all times leaves enough power for the sensor electronics, even at the bottom of the range.

The upper limit of 20 mA keeps power levels low, which suits intrinsically safe installations in hazardous areas, and gives a convenient 5:1 ratio with the 4 mA zero.

How to Convert 4-20 mA to Engineering Units

The 16 mA between 4 mA and 20 mA represents the full measuring range of the transmitter. To turn a current reading into a real value, work out how far along that 16 mA span the current is, then apply the same fraction to the measuring range:

Value = (Current − 4 mA) ÷ 16 mA × (Range Max − Range Min) + Range Min

Worked example: a pressure transmitter with a 0 to 150 psi range is reading 12 mA.

(12 − 4) ÷ 16 = 0.5, so the reading is 50% of the range. 0.5 × 150 psi = 75 psi.

The scale below shows the same relationship for the key points on the range:

4 mA

0% of range
0 psi

8 mA

25% of range
37.5 psi

12 mA

50% of range
75 psi

16 mA

75% of range
112.5 psi

20 mA

100% of range
150 psi

Advantages and Limitations of 4-20 mA

Advantages

Limitations

How Far Can a 4-20 mA Signal Travel?

Distance is limited by the loop’s voltage budget, not by signal loss. At 20 mA, every ohm in the loop drops a little voltage, and the transmitter still needs its minimum operating voltage (found on its datasheet, often around 8 to 12 V) across its terminals. The maximum total loop resistance is:

Max Loop Resistance (Ω) = (Supply Voltage − Transmitter Minimum Voltage) ÷ 0.020 A

Example: with a 24 V supply and a transmitter that needs 10 V, the loop can tolerate (24 − 10) ÷ 0.020 = 700 Ω. Subtract the 250 Ω receiver resistor and any displays or isolators, and what is left is available for cable. Typical 18 AWG instrument cable adds about 6.4 Ω per 1,000 ft of each conductor, so runs of several thousand feet are routine.

What Do Readings Below 4 mA or Above 20 mA Mean?

Many modern transmitters follow the NAMUR NE 43 recommendation, which reserves the currents just outside the normal range for diagnostics. This lets a control system tell a genuine out-of-range process value from a faulty instrument:

Not every transmitter supports NE 43, so check the datasheet before setting alarm limits in your PLC.

2-Wire, 3-Wire and 4-Wire 4-20 mA Devices

All three carry the same 4-20 mA signal. The difference is how the device gets its power:

  • 2-wire (loop-powered): power and signal share one pair. This is the most common design for pressure, level and temperature transmitters.
  • 3-wire: a separate supply wire powers the device, and the signal returns on a shared common. Used where the electronics need more power than a loop can provide.
  • 4-wire: fully separate power and signal pairs, often with AC mains power. Common on analyzers and flowmeters.

For step-by-step wiring diagrams, see How to Connect a 4-20 mA Pressure or Level Transmitter.

Products That Use 4-20 mA Signals

Most of the sensors and instruments we supply send or receive 4-20 mA. Browse the ranges below, or contact our engineers for help choosing.

Loop-powered 4-20 mA pressure transmitters and switches. View range

Submersible and hydrostatic level transmitters with 4-20 mA output. View range

RTD and thermocouple inputs converted to 4-20 mA. View range

Isolate, convert and split 4-20 mA, 0-10 V and other signals. View range

Loop-powered and panel meters that show 4-20 mA in real units. View range

Record 4-20 mA signals from multiple channels over time. View range

Frequently Asked Questions

It is a DC current. The loop is powered by a DC supply, typically 24 VDC, and the transmitter regulates the DC current between 4 and 20 mA.

A current stays the same everywhere in a series loop, so cable resistance and connections do not change the reading. A voltage signal such as 0-10 V loses accuracy over long cables and picks up more electrical noise.

Place a precision 250 Ω resistor across the input. Ohm’s law turns 4-20 mA into 1-5 V. For a 0-10 V input, or where the circuits must be electrically separated, use a signal converter instead.

Zero current means nothing is flowing, which almost always points to a broken wire, a loose terminal, a blown fuse or a missing power supply. A healthy loop never drops below about 3.6 mA.

Yes, by wiring the receivers in series, as long as the total loop resistance stays within the voltage budget. Where the receivers are on different grounds, use a signal splitter or isolator to avoid ground loops.

HART superimposes a small digital signal on top of the analog current. The 4-20 mA value is unaffected, but a HART-compatible device can also read diagnostics and configuration data over the same two wires.

More in This Category

2-Wire vs 3-Wire vs 4-Wire Transmitters: What Is the Difference?

All three transmit the same 4-20 mA signal. The difference is how they get power. A 2-wire transmitter draws its power from the signal loop itself. A 3-wire transmitter has a separate supply wire and shares a common return with the signal. A 4-wire transmitter has completely separate power and signal pairs, so it can use much more power, including AC mains.

4-20 mA vs 0-10 V: Which Analog Output Should You Choose?

Choose 4-20 mA for long cable runs, electrically noisy plants and anywhere you need to detect a broken wire. Choose 0-10 V for short runs inside a panel or machine, where its simpler wiring and direct compatibility with many controllers and drives are an advantage.

What Is HART, and How Does It Work Over a 4-20 mA Loop?

HART (Highway Addressable Remote Transducer) is a digital protocol that rides on top of a standard 4-20 mA signal. It superimposes a small, high-frequency signal on the loop current, so the analog value keeps working while a HART device can also exchange configuration settings, diagnostics and extra measurements over the same two wires.

Need help choosing the right product?

Our engineers can help you select, configure and integrate the right sensor, instrument or industrial computer for your application.