What Is a Ground Loop, and How Do I Prevent One?

The Short Answer

A ground loop happens when a signal circuit is connected to ground at two or more points that are at slightly different voltages. The difference drives an unwanted current through the signal wiring, which shows up as offset errors, noise or drifting readings. The cure is to break the loop with galvanic isolation or to ground the circuit at one point only.

Why Ground Loops Happen

In a real plant, the “ground” at a sensor in the field and the “ground” at the control panel are rarely at exactly the same voltage. Heavy currents from motors, welders and drives flowing through the grounding system create voltage differences of a few millivolts to several volts. If the signal circuit is grounded at both ends, that voltage difference pushes current around the loop formed by the signal wiring and the ground.

Common Symptoms

How to Prevent Ground Loops

Why Isolation Works

A galvanic isolator passes the signal across a barrier using a transformer, optocoupler or capacitive coupling, with no direct electrical path between input and output. Because there is no conductor for current to flow through, the loop is broken, while the measurement itself passes through unchanged. Isolators also protect equipment against surges and allow one signal to feed devices on different grounds.

Related Products

Isolated signal converters are the most reliable way to eliminate ground loops in analog signals.

Galvanically isolated converters and splitters. View range

Isolated serial connectivity for RS-485 networks. View range

Isolated analog and digital I/O. View range

Frequently Asked Questions

Yes. Large ground potential differences, especially during faults or lightning, can drive enough current to damage input circuits and communication ports.

Not exactly. A ground loop is one cause of noise and offset. Other causes include poor shielding and running signal cables next to power cables.

It is less likely, but it can still happen if the sensor body is grounded and the loop is also grounded at the receiver. An isolator removes the risk.

More in This Category

What Is a 4-20 mA Signal?

A 4-20 mA signal is an analog DC current that represents a measured value, with 4 mA at the bottom of the range and 20 mA at the top. Because it is a current rather than a voltage, it travels long distances without losing accuracy, and the same two wires can power the sensor.

2-Wire vs 3-Wire vs 4-Wire Transmitters: What Is the Difference?

All three transmit the same 4-20 mA signal. The difference is how they get power. A 2-wire transmitter draws its power from the signal loop itself. A 3-wire transmitter has a separate supply wire and shares a common return with the signal. A 4-wire transmitter has completely separate power and signal pairs, so it can use much more power, including AC mains.

4-20 mA vs 0-10 V: Which Analog Output Should You Choose?

Choose 4-20 mA for long cable runs, electrically noisy plants and anywhere you need to detect a broken wire. Choose 0-10 V for short runs inside a panel or machine, where its simpler wiring and direct compatibility with many controllers and drives are an advantage.

Need help choosing the right product?

Our engineers can help you select, configure and integrate the right sensor, instrument or industrial computer for your application.