What Is HART, and How Does It Work Over a 4-20 mA Loop?

The Short Answer

HART (Highway Addressable Remote Transducer) is a digital protocol that rides on top of a standard 4-20 mA signal. It superimposes a small, high-frequency signal on the loop current, so the analog value keeps working while a HART device can also exchange configuration settings, diagnostics and extra measurements over the same two wires.

How HART Works

HART uses frequency shift keying (FSK) based on the Bell 202 standard. A 1,200 Hz tone represents a binary 1 and a 2,200 Hz tone represents a binary 0. The tones are only about ±0.5 mA in amplitude and average to zero, so the 4-20 mA reading seen by the control system is not affected.

Communication runs at 1,200 bits per second in a master-slave arrangement. The control system or a handheld communicator is the master, and the field instrument answers its requests.

What You Can Do With HART

Wiring Requirements

HART needs a minimum loop resistance, typically 250 Ω, so the digital signal can develop a readable voltage. Many PLC inputs already include a 250 Ω resistor. A handheld communicator connects across this resistor or across the transmitter terminals. Use twisted, shielded cable and keep within the cable length and capacitance limits given in the instrument manual.

Point-to-Point and Multidrop

Point-to-point

Multidrop

HART Compared With Other Protocols

HART keeps the familiar 4-20 mA wiring, which makes it easy to adopt in existing plants. Fully digital networks such as Modbus RS-485, PROFIBUS PA or Foundation Fieldbus carry more data and connect more devices per cable, but they require new infrastructure. WirelessHART extends the same command set to battery-powered wireless instruments.

Related Products

Several of our pressure and level transmitters offer HART communication alongside the 4-20 mA output.

4-20 mA transmitters with optional HART. View range

Hydrostatic level transmitters with HART options. View range

Isolate 4-20 mA loops between systems. View range

Frequently Asked Questions

No. The HART signal averages to zero, so the analog value seen by the PLC or meter is unaffected.

Standard twisted, shielded instrument cable works. Check the instrument manual for maximum cable length and capacitance.

Only if it is specified as HART-transparent. Standard isolators can block or distort the digital signal.

More in This Category

What Is a 4-20 mA Signal?

A 4-20 mA signal is an analog DC current that represents a measured value, with 4 mA at the bottom of the range and 20 mA at the top. Because it is a current rather than a voltage, it travels long distances without losing accuracy, and the same two wires can power the sensor.

2-Wire vs 3-Wire vs 4-Wire Transmitters: What Is the Difference?

All three transmit the same 4-20 mA signal. The difference is how they get power. A 2-wire transmitter draws its power from the signal loop itself. A 3-wire transmitter has a separate supply wire and shares a common return with the signal. A 4-wire transmitter has completely separate power and signal pairs, so it can use much more power, including AC mains.

4-20 mA vs 0-10 V: Which Analog Output Should You Choose?

Choose 4-20 mA for long cable runs, electrically noisy plants and anywhere you need to detect a broken wire. Choose 0-10 V for short runs inside a panel or machine, where its simpler wiring and direct compatibility with many controllers and drives are an advantage.