2-Wire vs 3-Wire vs 4-Wire RTD Connections

The Short Answer

The number of wires decides how well the instrument can cancel the resistance of the leads. A 2-wire RTD adds the full lead resistance to the reading, causing errors on anything but very short runs. A 3-wire RTD compensates for lead resistance and is the industrial standard. A 4-wire RTD removes lead effects completely and is used for laboratory and calibration-grade accuracy.

Why Lead Resistance Matters

A Pt100 changes by only about 0.385 Ω per °C. Copper lead wires add their own resistance, and the instrument cannot tell it apart from the sensor. With 2-wire wiring, every ohm of lead resistance reads as about 2.6 °C of error.

Error (°C) ≈ Total lead resistance (Ω) ÷ 0.385

2-Wire Connection

One wire runs to each end of the element, and the instrument measures the total resistance of the element and both leads. It is only acceptable for very short leads, Pt1000 sensors (where the lead resistance is proportionally ten times smaller), or where a head-mounted transmitter sits right at the sensor.

3-Wire Connection

A third wire connects to one end of the element. The instrument uses it to measure the resistance of one lead and subtracts it, on the assumption that all three leads are equal. This cancels most of the lead error and is the standard for industrial installations.

4-Wire Connection

Two wires carry a precise excitation current through the element, and two separate wires measure the voltage across it. Almost no current flows in the measuring leads, so their resistance has no effect at all. This is the most accurate method, used in laboratories, calibration and high-accuracy process measurement.

Which Should You Use?

Recommended

Avoid

Related Products

Our transmitters and instruments accept 2-, 3- and 4-wire RTD connections.

Head and DIN-rail transmitters for RTDs. View range

Controllers with 3-wire RTD inputs. View range

Multichannel RTD logging. View range

Frequently Asked Questions

Yes. Leave one of the duplicate leads disconnected. You lose the extra accuracy but keep 3-wire compensation.

Yes, by joining the two same-colored leads, but lead resistance will add error.

Under IEC 60751, one end of the element uses red leads and the other uses white. Duplicate leads share the same color.

More in This Category

RTD vs Thermocouple vs Thermistor: Which Temperature Sensor Should You Use?

Use an RTD when you need accuracy and long-term stability up to about 600 °C (1,100 °F). Use a thermocouple for high temperatures, fast response or low cost, up to about 1,700 °C (3,100 °F). Use a thermistor for very precise measurement over a narrow, low temperature range, such as in electronics and HVAC.

What Is a Pt100 RTD, and What Do Class A and Class B Mean?

A Pt100 is a platinum resistance temperature detector with a resistance of exactly 100 Ω at 0 °C, rising by about 0.385 Ω per °C. Its tolerance class, defined in IEC 60751, tells you how accurate it is. Class A is ±0.15 °C at 0 °C, and Class B is ±0.3 °C at 0 °C, with the tolerance widening as temperature moves away from zero.

Thermocouple Types (J, K, T, E, N) and Cold Junction Compensation Explained

Each thermocouple type uses a different pair of metals, which sets its temperature range and best uses. Type K is the general-purpose choice up to about 1,260 °C. Type J suits lower temperatures and reducing atmospheres, Type T is best for low and cryogenic temperatures, and Types R and S cover very high temperatures. Every thermocouple measures relative to its cold junction, so the instrument must apply cold junction compensation.

Need help choosing the right product?

Our engineers can help you select, configure and integrate the right sensor, instrument or industrial computer for your application.