The Short Answer
The number of wires decides how well the instrument can cancel the resistance of the leads. A 2-wire RTD adds the full lead resistance to the reading, causing errors on anything but very short runs. A 3-wire RTD compensates for lead resistance and is the industrial standard. A 4-wire RTD removes lead effects completely and is used for laboratory and calibration-grade accuracy.
Why Lead Resistance Matters
A Pt100 changes by only about 0.385 Ω per °C. Copper lead wires add their own resistance, and the instrument cannot tell it apart from the sensor. With 2-wire wiring, every ohm of lead resistance reads as about 2.6 °C of error.
Error (°C) ≈ Total lead resistance (Ω) ÷ 0.385
2-Wire Connection
One wire runs to each end of the element, and the instrument measures the total resistance of the element and both leads. It is only acceptable for very short leads, Pt1000 sensors (where the lead resistance is proportionally ten times smaller), or where a head-mounted transmitter sits right at the sensor.
3-Wire Connection
A third wire connects to one end of the element. The instrument uses it to measure the resistance of one lead and subtracts it, on the assumption that all three leads are equal. This cancels most of the lead error and is the standard for industrial installations.
- Good accuracy over long cable runs.
- Relies on all leads having matched resistance. Corroded terminals or mixed wire gauges cause errors.
4-Wire Connection
Two wires carry a precise excitation current through the element, and two separate wires measure the voltage across it. Almost no current flows in the measuring leads, so their resistance has no effect at all. This is the most accurate method, used in laboratories, calibration and high-accuracy process measurement.
Which Should You Use?
Recommended
- 3-wire for most industrial process measurement.
- 4-wire for laboratory, calibration and custody transfer.
- A head-mounted transmitter for long runs.
Avoid
- 2-wire Pt100 over long cable runs.
- Mixing wire gauges in a 3-wire circuit.
- Connecting a 4-wire sensor as 2-wire.
Related Products
Our transmitters and instruments accept 2-, 3- and 4-wire RTD connections.
Frequently Asked Questions
Can I connect a 4-wire RTD to a 3-wire input?
Yes. Leave one of the duplicate leads disconnected. You lose the extra accuracy but keep 3-wire compensation.
Can I connect a 3-wire RTD to a 2-wire input?
Yes, by joining the two same-colored leads, but lead resistance will add error.
What colors are RTD wires?
Under IEC 60751, one end of the element uses red leads and the other uses white. Duplicate leads share the same color.