The Short Answer
Use an RTD when you need accuracy and long-term stability up to about 600 °C (1,100 °F). Use a thermocouple for high temperatures, fast response or low cost, up to about 1,700 °C (3,100 °F). Use a thermistor for very precise measurement over a narrow, low temperature range, such as in electronics and HVAC.
RTD (Resistance Temperature Detector)
An RTD is a platinum element whose resistance rises predictably with temperature. The most common type, the Pt100, measures 100 Ω at 0 °C. RTDs are accurate, repeatable and stable for years, which makes them the standard choice for process measurement.
Thermocouple
A thermocouple is two dissimilar metal wires joined at the tip. A temperature difference between the tip and the other end generates a small voltage. Thermocouples are inexpensive, rugged, respond quickly and reach very high temperatures, but they are less accurate and drift more than RTDs.
Thermistor
A thermistor is a ceramic semiconductor whose resistance changes sharply with temperature, usually decreasing as temperature rises (NTC). That sensitivity gives excellent resolution, but only over a limited range, typically -50 to 150 °C, and the response is highly non-linear.
Side-by-Side Comparison
RTD
- Range: about -200 to 600 °C.
- Accuracy: high, ±0.15 °C (Class A at 0 °C).
- Stability: excellent.
- Cost: moderate.
Thermocouple
- Range: about -200 to 1,700 °C by type.
- Accuracy: ±1 to 2 °C typical.
- Stability: drifts over time at high temperatures.
- Cost: low.
Thermistor
- Range: about -50 to 150 °C.
- Accuracy: very high in a narrow band.
- Stability: good.
- Cost: low.
How to Choose
- Above 600 °C: thermocouple.
- Process control, food, pharma or energy measurement: RTD.
- Fast-changing surfaces or exhaust gas: thermocouple.
- Electronics, appliances and HVAC: thermistor.
- Long cable runs: add a temperature transmitter to convert to 4-20 mA.
Related Products
We supply temperature transmitters and the instruments that read RTD and thermocouple inputs directly.
Frequently Asked Questions
Which is more accurate, an RTD or a thermocouple?
An RTD. A Class A Pt100 is accurate to ±0.15 °C at 0 °C, while a standard thermocouple is typically ±1 to 2 °C.
Which responds faster?
A small exposed-junction thermocouple usually responds fastest, because its tip has very little mass.
Can I replace a thermocouple with an RTD?
Only if the temperature is within the RTD range and the instrument input is changed to suit, since the two produce completely different signals.