Thermocouple Types (J, K, T, E, N) and Cold Junction Compensation Explained

The Short Answer

Each thermocouple type uses a different pair of metals, which sets its temperature range and best uses. Type K is the general-purpose choice up to about 1,260 °C. Type J suits lower temperatures and reducing atmospheres, Type T is best for low and cryogenic temperatures, and Types R and S cover very high temperatures. Every thermocouple measures relative to its cold junction, so the instrument must apply cold junction compensation.

Common Thermocouple Types

How a Thermocouple Works

When two different metals are joined and the junction is heated, a small voltage appears across the free ends. This is the Seebeck effect. The voltage is tiny, roughly 41 µV per °C for Type K, and depends on the temperature difference between the hot (measuring) junction and the cold (reference) junction where the wires connect to the instrument.

Cold Junction Compensation

Because the voltage depends on a temperature difference, the instrument must know the temperature at its own terminals. It measures that with a built-in sensor and adds the equivalent voltage back, so the result reflects the true hot junction temperature. This is cold junction compensation (CJC).

Measured temperature = Thermocouple reading + Cold junction temperature

Use the Right Extension Wire

Every connection between dissimilar metals forms a new junction. Run matching thermocouple or extension wire all the way to the instrument, and use thermocouple connectors of the same type. Ordinary copper wire creates extra junctions and errors that change with ambient temperature.

Related Products

Our instruments accept all common thermocouple types with automatic cold junction compensation.

Convert thermocouple signals to 4-20 mA. View range

Controllers with universal thermocouple inputs. View range

Log thermocouple channels over time. View range

Frequently Asked Questions

Type K, because it covers a wide range at low cost and suits most oxidizing environments.

The instrument is still applying cold junction compensation, so an open circuit may show ambient temperature or trigger a burnout alarm.

No. Copper creates new junctions that introduce errors. Use matching thermocouple extension wire.

More in This Category

RTD vs Thermocouple vs Thermistor: Which Temperature Sensor Should You Use?

Use an RTD when you need accuracy and long-term stability up to about 600 °C (1,100 °F). Use a thermocouple for high temperatures, fast response or low cost, up to about 1,700 °C (3,100 °F). Use a thermistor for very precise measurement over a narrow, low temperature range, such as in electronics and HVAC.

What Is a Pt100 RTD, and What Do Class A and Class B Mean?

A Pt100 is a platinum resistance temperature detector with a resistance of exactly 100 Ω at 0 °C, rising by about 0.385 Ω per °C. Its tolerance class, defined in IEC 60751, tells you how accurate it is. Class A is ±0.15 °C at 0 °C, and Class B is ±0.3 °C at 0 °C, with the tolerance widening as temperature moves away from zero.

2-Wire vs 3-Wire vs 4-Wire RTD Connections

The number of wires decides how well the instrument can cancel the resistance of the leads. A 2-wire RTD adds the full lead resistance to the reading, causing errors on anything but very short runs. A 3-wire RTD compensates for lead resistance and is the industrial standard. A 4-wire RTD removes lead effects completely and is used for laboratory and calibration-grade accuracy.