How Do I Choose Accelerometer Sensitivity (100 mV/g vs 500 mV/g)?

The Short Answer

Use 100 mV/g for most general machinery, such as motors, pumps and fans. Choose 500 mV/g or higher for slow-speed machines and very low vibration levels, where you need more signal above the noise floor. Choose 10 mV/g or lower for high-amplitude vibration and shock, where a sensitive sensor would saturate.

The Trade-Off

Sensitivity and measuring range are linked. An IEPE sensor can swing its output by about ±5 V around its bias voltage, so a higher sensitivity means a smaller range:

Measuring range (g) ≈ Output swing (V) ÷ Sensitivity (V/g)

10 mV/g

±500 g
shock, impact

100 mV/g

±50 g
general machinery

500 mV/g

±10 g
slow speed, low level

When to Choose 100 mV/g

This is the industry standard for condition monitoring. It gives a good balance of range and resolution for machines running between about 600 and 3,600 rpm, and it matches the default settings of most portable analyzers and online systems.

When to Choose a Higher Sensitivity

At low frequencies, the acceleration from a given displacement is very small, so a high-sensitivity, low-noise sensor is needed to see it.

When to Choose a Lower Sensitivity

Other Things to Check

Related Products

Our accelerometer range covers low-frequency, general-purpose and high-g sensors.

Sensors from 10 mV/g to 500 mV/g and beyond. View range

Direct shaft vibration measurement. View range

Dynamic signal acquisition hardware. View range

Frequently Asked Questions

Yes, if the vibration stays within its ±10 g range. On machines with high-frequency gear or bearing energy it may overload.

Not exactly. It gives a stronger signal relative to noise, which improves resolution at low levels, but it reduces the measuring range.

The smallest vibration it can resolve, usually given in µg per root hertz. Lower is better for slow-speed machinery.

More in This Category

How Does a Piezoelectric Accelerometer Work?

A piezoelectric accelerometer contains a small mass resting on a piezoelectric crystal. When the machine vibrates, the mass presses on the crystal with a force proportional to the acceleration, and the crystal produces a matching electrical charge. Built-in electronics convert this charge into a voltage signal, typically 100 mV per g, that represents the vibration.

What Is IEPE (ICP), and How Is an IEPE Sensor Powered?

IEPE (Integrated Electronics Piezo-Electric) describes a vibration sensor with a built-in amplifier that is powered and read over the same two wires. The input supplies a constant current, typically 2 to 10 mA, from an 18 to 30 V source. The sensor sits at a DC bias voltage of around 10 to 12 V, and the vibration signal rides on top of it. ICP is a trademarked name for the same technology.

How Should I Mount an Accelerometer? Stud, Adhesive and Magnet Compared

Stud mounting to a flat, spot-faced surface gives the best high-frequency response and is the choice for permanent installations. Adhesive mounting to a mounting pad is a good alternative where you cannot drill. Magnet mounting is quick and suits portable data collection, but it limits the usable frequency range.

Need help choosing the right product?

Our engineers can help you select, configure and integrate the right sensor, instrument or industrial computer for your application.