SLS-CA Ceramic Submersible Level Sensor, Analog Output

The SLS-CA is a submersible level sensor with a ceramic (Al2O3) piezo-resistive sensing element, chosen for its chemical resistance and robustness in wastewater, saline and other aggressive liquids. The housing is available in 316 stainless steel or marine bronze CA104, and a high-integrity cable gland allows permanent submersion to 100 m (328 ft).

Level ranges run from 5 to 100 mWG with accuracy of ≤ ±0.25% or ≤ ±0.15% FS. Outputs include 4-20 mA, 0-5 V, 0-10 V and 0.5-4.5 V ratiometric, conditioned by a 16-bit microprocessor, or a raw millivolt signal for low-power systems, with an optional temperature output.

Key Features Of The SLS-CA Ceramic Submersible Level Sensor

  1. Ceramic Al2O3 Sensing Element
    A ceramic diaphragm resists chemical attack and abrasion in wastewater and aggressive liquids.

  2. Stainless Steel Or Marine Bronze
    Choose 316 stainless steel, or marine bronze CA104 for seawater and saline environments.

  3. Submersible To 100 m
    IP68 protection with a high-integrity cable gland and PUR cable.

  4. Choice Of Analog Outputs
    4-20 mA, 0-5 V, 0-10 V, 0.5-4.5 V ratiometric or raw millivolt.

  5. 16-Bit Digital Compensation
    Linearization and temperature compensation for accuracy of ≤ ±0.25% or ≤ ±0.15% FS.

  6. Optional Temperature Output
    Add liquid temperature monitoring without a second sensor.

Applications For Ceramic Submersible Level Sensors

The SLS-CA is the choice for level measurement in liquids that are harder on a sensor:

  • Wastewater and sewage – level measurement in wet wells, sumps and treatment tanks.
  • Seawater and brackish water – harbor, estuary and coastal monitoring with the marine bronze housing.
  • Rivers, reservoirs and boreholes – water level monitoring where sediment is present.
  • Tank, IBC and tote level – hydrostatic level measurement of compatible process liquids.
  • V-notch weir flow measurement – head measurement for open-channel flow.
  • Flood defense monitoring – level monitoring in demanding outdoor sites.
  • Telemetry and data logging – 4-20 mA and low-power outputs for remote stations.

Ceramic Or Silicon: Which Level Sensor Should You Choose?

Both technologies measure hydrostatic pressure, but they suit different liquids. A silicon sensor sits behind a thin stainless steel isolating diaphragm and offers the highest sensitivity, making it the better choice for clean water and shallow ranges. A ceramic sensor uses a thick, flush Al2O3 diaphragm that is exposed directly to the liquid.

That ceramic diaphragm is highly resistant to corrosion and abrasion and is easy to clean, which is why the SLS-CA is preferred for wastewater, sludge, seawater and liquids carrying solids. Combined with a marine bronze CA104 housing, which resists saltwater corrosion, it is well suited to coastal and marine installations.

Output Options And Supply Voltages

OutputWiringSupply VoltageCurrent
4-20 mA2-wire8 to 32 VDCSignal dependent
0-5 V or 0-10 V3-wire12 to 32 VDC6 mA
0.5-4.5 V ratiometric3-wire2.7 to 5.5 VDC2.5 mA
Raw millivoltPassive bridgeFor low-power applications

Level Ranges

Ranges are specified in meters of water gauge (mWG).

Range (mWG)Approx. Depth (ft of water)
516.4
1032.8
2065.6
3098.4
50164
100328

SLS-CA Submersible Level Sensor Technical Specifications

SpecificationDetail
Product TypeCeramic submersible hydrostatic level sensor, analog output
Sensor TechnologyCeramic (Al2O3) piezo-resistive
Level Ranges5, 10, 20, 30, 50, 100 mWG
Pressure ReferenceGauge (standard), sealed gauge, absolute
Accuracy≤ ±0.25% or ≤ ±0.15% FS
Safe Overpressure1.5 x rated range
Burst Pressure3 x rated range
Long Term Stability≤ ±0.10% FS
Output Options4-20 mA (2-wire); 0-5 V, 0-10 V (3-wire); 0.5-4.5 V ratiometric (3-wire); raw millivolt
Supply Voltage8 to 32 VDC (4-20 mA); 12 to 32 VDC (voltage); 2.7 to 5.5 VDC (ratiometric)
Response Time< 10 ms
Thermal Effects±0.015% FS/°C
Temperature OutputOptional
Housing Material316 stainless steel or marine bronze CA104
Sensor MaterialCeramic Al2O3
SealsFKM, EPDM or NBR
Compensated Temperature0 to +40 °C
Media Temperature-10 to +60 °C, non-freezing
CablePUR submersible cable with internal vent tube, terminated in tails
Cable ConnectionG1/4 DIN 3852 male thread when nose cone is unscrewed
Ingress ProtectionIP68, fully submersible to 100 m
Surge ProtectionInternal protection; external protection devices recommended
WeightSensor < 270 g; cable 48 g per meter
ConformityCE
AccessoriesNPT threaded adaptor, vented junction box, cable hanger

SLS-CA Ceramic Submersible Level Sensor FAQs

When should I choose a ceramic level sensor?

Choose ceramic for wastewater, seawater, sludge and liquids carrying solids. The ceramic diaphragm resists corrosion and abrasion better than a thin metal isolating diaphragm.

When is the marine bronze housing needed?

Marine bronze CA104 is recommended for seawater and saline or brackish water, where it resists corrosion better than stainless steel.

What is the lowest range of the SLS-CA?

The lowest standard range is 5 mWG (about 16 ft of water). For shallower ranges from 0.5 mWG, choose the silicon-sensor SLS-SA.

Can the SLS-CA be used in drinking water or clean water?

Yes, it works in clean water too, although the silicon SLS-SA offers higher accuracy and lower ranges for those applications.

Please submit your product enquiry

Thank you for visiting Diversified Tech.

Please fill in the form and send through your enquiry. If you are interested in multiple products then please add the details into the message section.

We look forward to receiving your enquiry.

Thank you