CTC DD100170 8 mm Proximity Probe Driver

The DD100170 Series is an 8 mm eddy current probe driver designed for machinery monitoring applications that require a 4–20 mA current loop output proportional to dynamic displacement. In this configuration, the current loop both powers the driver and transmits the measurement signal, making the unit well suited for direct integration with PLCs, DCS platforms, and other industrial monitoring systems. This makes it a practical choice for vibration monitoring on rotating assets where robust analog transmission and simplified wiring are important.

In addition to its 4–20 mA functionality, the DD100170 also provides isolated voltage output at both a BNC connection and a 4-position terminal block using Vout and Com, allowing convenient access for commissioning and diagnostics. The driver features a durable aluminum enclosure, an upgraded SecureLock probe connector for improved retention, and an operating input range of -17.5 to -30 VDC. It supports a linear range of 10–90 mils (0.25–2.30 mm) with a nominal sensitivity of -200 mV/mil (-7.87 V/mm), while the datasheet notes that current is 180 degrees out of phase for this 4–20 mA driver.

SKU DD100170 Category

Core Advantages of the DD100170 Series

  1. Current Loop Output for Dynamic Displacement Measurement

    • The driver provides a 4–20 mA output proportional to dynamic displacement, making it suitable for standard process monitoring and machinery condition systems.
  2. Combined Power and Signal Through One Loop

    • The 4–20 mA loop powers the device while also carrying the measurement signal, helping reduce wiring complexity in panel and field installations.
  3. Isolated Voltage Output for Setup and Verification

    • Standard isolated voltage output is available through both BNC and terminal block (Vout, Com) connections for commissioning, testing, and troubleshooting.
  4. SecureLock Connector for Improved Connection Stability

    • The upgraded SecureLock probe connector helps maintain a dependable electrical connection in high-vibration environments.
  5. Linear Measurement Range Suited to 8 mm Probe Systems

    • With a 10–90 mil (0.25–2.30 mm) linear range and defined nominal scaling, the driver supports consistent monitoring performance.
  6. Industrial Construction for Panel-Mounted Systems

    • The aluminum enclosure and compact form factor make the unit suitable for machinery monitoring cabinets, skids, and protection system panels.

Technical Specifications for the DD100170 Eddy Current Driver

ParameterSpecification
Model / SeriesDD100170 Series
Product TypeEddy current probe driver
System Compatibility8 mm proximity probe systems
Primary Output4–20 mA current loop
4–20 mA Output Proportional ToDynamic displacement
Voltage OutputIsolated voltage output
Voltage Output ConnectionsBNC and terminal block (Vout, Com)
Probe ConnectorSecureLock
Power & Output Connector4-position terminal block & BNC
Input Voltage-17.5 to -30 VDC
Linear Range10–90 mils (0.25–2.30 mm)
Nominal Voltage Output-200 mV/mil (-7.87 V/mm)
Temperature Range-49 to 185°F (-45 to 85°C)
Enclosure MaterialAluminum
Phase NoteCurrent is 180 degrees out of phase for 4–20 mA driver
Approx. Footprint2.36 in × 2.00 in (60.3 mm × 50.8 mm)
Approx. Height3.36 in (85.3 mm), overall shown to 3.59 in (91.3 mm)
Mounting Holes4 × Ø0.18 in (Ø4.5 mm)
Build StatusBuilt to order

Recommended Applications for the DD100170 Series

The DD100170 Series is well suited to rotating equipment installations that need a dynamic displacement signal delivered as a 4–20 mA output for industrial monitoring and control systems. Its combination of loop-powered operation, isolated voltage access, and secure probe connectivity makes it useful in both new installations and retrofit projects.

  • Dynamic displacement monitoring on pumps, compressors, turbines, and motors
  • Machinery vibration channels tied directly into PLC or DCS analog inputs
  • Condition monitoring systems requiring current-loop signal transmission
  • Skid-mounted rotating equipment packages needing compact driver hardware
  • Retrofit monitoring upgrades replacing older 8 mm driver assemblies
  • Commissioning and diagnostic workflows using BNC or terminal block voltage outputs
  • High-vibration industrial environments where connector retention is important

Please submit your product enquiry

Thank you for visiting Diversified Tech.

Please fill in the form and send through your enquiry. If you are interested in multiple products then please add the details into the message section.

We look forward to receiving your enquiry.

Thank you