Key Features of the DD100970 Series
4–20 mA Output Proportional to Dynamic Displacement
- Provides loop-powered current output for dynamic displacement measurement, ideal for standard industrial analog input integration.
Loop-Powered Architecture for Simplified Wiring
- The same current loop powers the driver and transmits the signal, supporting robust, noise-tolerant transmission across typical plant wiring runs.
Isolated Voltage Output for Commissioning Access
- Isolated voltage output is available at both BNC and terminal block (
Vout/Com) for verification, troubleshooting, and supplemental monitoring.
- Isolated voltage output is available at both BNC and terminal block (
SecureLock Probe Connector Upgrade
- SecureLock connector improves retention and serviceability in high-vibration monitoring applications.
FFV Measurement Range Support
- Supports a 10–70 mils (0.25–1.78 mm) linear range with defined nominal scaling for consistent channel behavior.
Industrial Aluminum Enclosure
- Aluminum housing supports durable installation in monitoring panels, machinery skids, and protective enclosures.
Technical Specifications for the DD100970 Series
| Parameter | Specification |
|---|---|
| Model / Series | DD100970 Series |
| Device Type | FFV proximity probe driver for eddy current probe |
| Output (Primary) | 4–20 mA current loop |
| 4–20 mA Output Proportional To | Dynamic displacement |
| Phase Note | Current is 180° out of phase for 4–20 mA driver |
| Voltage Output | Isolated voltage output (standard) |
| Voltage Output Connections | BNC and terminal block (Vout, Com) |
| Probe Connector | SecureLock |
| Power & Output Connector | 4-position terminal block & BNC |
| Input Voltage | -17.5 to -30 VDC |
| Linear Range | 10–70 mils (0.25–1.78 mm) |
| Nominal Sensitivity | -200 mV/mil (-7.87 V/mm) |
| Temperature Range | -49 to 185°F (-45 to 85°C) |
| Enclosure Material | Aluminum |
| Approx. Footprint | 2.38 in (60.3 mm) × 2.00 in (50.8 mm) (per drawing) |
| Approx. Height | 3.36 in (85.3 mm); max shown 3.59 in (91.3 mm) |
| Mounting Holes | 4 × Ø0.18 in (Ø4.5 mm) |
| Supply Status | Built to order |
Suitable Applications for the DD100970 Series
The DD100970 is well-suited to rotating equipment monitoring systems that need a dynamic displacement signal delivered as a robust 4–20 mA current loop for direct control-system integration, while maintaining voltage output access for commissioning and validation.
- Dynamic displacement monitoring into PLC/DCS analog input channels
- Condition monitoring of pumps, compressors, turbines, and motors in critical service
- Long cable runs where current-loop signaling improves noise immunity
- Monitoring panel retrofits standardizing on 4–20 mA machinery signals
- Skid-mounted rotating equipment packages requiring simplified loop wiring
- Commissioning and troubleshooting using BNC/
Voutoutputs - Industrial environments where SecureLock connectors reduce maintenance events